Re: Anyone add a 2nd heat zone to their house?
Posted 3/1/2013 8:10:33 PM by Scott What you want to do is to check the air vents on the radiator. Since these radiators are the last ones on the run they should have the biggest holes in the vent to release the air faster and get the steam to them faster. This way they heat up and the other ones that are closer heat up slower. The pipes and radiator stay air bound then as the steam fills the radiator it pushes the air out. Youcan take the name off the valve it could be Hoffman or Gorton those are the better ones. The valave screws in most likely it is an angle valve and that should 1/4 inch. You want to go as big as possible. This would be the cheapest way to go.Maybe 20.00 for both from the plumbing supply house. Scott |